THE BILL ITSELF
HB 1377
Water Safety for Cooling Towers, Domestic Water Holding Tanks, and Supplemental Disinfection Systems
1
A bill to be entitled
2
An act relating to water safety for cooling towers,
3
domestic water holding tanks, and supplemental
4
disinfection systems; creating part III of ch. 386,
5
F.S., entitled "Water Safety for Cooling Towers,
6
Domestic Water Holding Tanks, and Supplemental
7
Disinfection Systems"; creating s. 386.301, F.S.;
8
providing legislative intent; creating s. 386.302,
9
F.S.; providing definitions; creating s. 386.303,
10
F.S.; requiring that owners of cooling towers,
11
domestic water holding tanks, and supplemental
12
disinfection systems register them with the Department
13
of Health; requiring the department to create a
14
statewide electronic system for such registrations;
15
providing minimum requirements for the registration
16
system; requiring that owners of cooling towers,
17
domestic water holding tanks, or supplemental
18
disinfection systems report specified information to
19
the department beginning on a specified date;
20
providing department responsibilities regarding the
21
registration system; requiring that owners of cooling
22
towers maintain certain records for a specified
23
timeframe; requiring that a copy of the maintenance
24
program and plan be kept on the cooling tower
25
premises; providing construction; creating s. 386.304,
26
F.S.; requiring that owners of cooling towers obtain
27
or update a maintenance program and plan for existing
28
and newly installed cooling towers by a specified
29
date; providing requirements for the maintenance
30
program and plan; creating s. 386.305, F.S.; requiring
31
that certain culture analyses be conducted by
32
certified environmental laboratories; providing
33
requirements for interpreting the results of such
34
analyses; creating s. 386.306, F.S.; requiring that
35
owners of cooling towers provide notification to the
36
county health department and the public within a
37
specified timeframe under specified circumstances;
38
requiring county health departments to provide certain
39
notification to the department; requiring the county
40
health department or, at its discretion, the
41
department to determine the method of certain
42
notifications; creating s. 386.307, F.S.; providing
43
cooling tower disinfection standards; requiring that
44
the person conducting the disinfection meet certain
45
qualifications; specifying the types of products that
46
may be used during a disinfection; providing cooling
47
tower efficiency standards; creating s. 386.308, F.S.;
48
requiring that owners of cooling towers have the
49
cooling towers inspected before initial startup and,
50
thereafter, at specified intervals; providing
51
inspection requirements; requiring that persons
52
conducting inspections report deficiencies to the
53
owner for corrective action; requiring initial and
54
annual certification of cooling towers by a specified
55
date; providing requirements for certification;
56
requiring that all inspection findings, deficiencies,
57
corrective actions, and certifications be reported to
58
the department and maintained by the owner; creating
59
s. 386.309, F.S.; authorizing the department or a
60
county health department to require an owner to
61
conduct a Legionella culture sampling and analysis
62
under certain circumstances; authorizing an officer,
63
employee, or agent of the department or county health
64
department to enter a property to inspect a cooling
65
tower; specifying that certain actions by the owner of
66
a cooling tower may constitute a nuisance; providing
67
for civil and criminal penalties; requiring the State
68
Surgeon General to submit a report to the Legislature
69
by a specified date; providing requirements for the
70
report; creating s. 386.3101, F.S.; authorizing county
71
health departments or the department to issue waivers
72
if the waiver does not present a danger to the public
73
health; providing requirements for the waivers;
74
authorizing county health departments to issue
75
variances under certain circumstances for a specified
76
period of time; providing an effective date.
78
Be It Enacted by the Legislature of the State of Florida: Section 1. Part III of chapter 386, Florida Statutes,
81
consisting of ss. 386.301-386.3101, Florida Statutes, is created
82
and entitled "Water Safety for Cooling Towers, Domestic Water
83
Holding Tanks, and Supplemental Disinfection Systems."
84
Section 2. Section 386.301, Florida Statutes, is created
85
to read:
86
386.301 Legislative intent.—The purpose of this part is to
87
protect people from the health hazards of Legionella, a
88
bacterium that is known to originate in improperly sanitized
89
cooling towers, domestic water holding tanks, and building
90
piping systems.
91
Section 3. Section 386.302, Florida Statutes, is created
92
to read:
93
386.302 Definitions.—As used in this part, the term:
94
(1) "Bacteriological culture sampling and analysis" means
95
the collection of a water sample for the purpose of measuring
96
the live culture growth of aerobic bacterial populations using
97
heterotrophic plate count, dip slides, or a similar method
98
employed by the industry in accordance with the manufacturer's
99
directions for use.
100
(2) "Building," unless otherwise expressly indicated by
101
the text, means all or part of a structure, premises, or lot
102
which is used or is intended to support or shelter a use or
103
occupancy.
104
(3) "Cleaning" means physical, mechanical, or other
105
removal of biofilm, scale, debris, rust, other corrosion
106
products, sludge, algae, and other potential sources of
107
contamination.
108
(4) "Compliance inspection" means the inspection, testing,
109
and other activities that are required on a regular basis in
110
accordance with s. 386.308.
111
(5) "Cooling tower" means an evaporative condenser, a
112
fluid cooler, or another wet cooling device that is capable of
113
aerosolizing water; that contains or is part of a recirculated
114
water system; and that is incorporated into a building's cooling
115
process, industrial process, refrigeration system, or energy
116
production system.
117
(6) "Cooling tower cells" means the smallest subdivisions
118
of a tower which can function independently with regard to air
119
and water flow. Each cell may have one or more fans and one or
120
more distribution systems.
121
(7) "Cooling tower water system" means one or more cooling
122
towers and all of the recirculating water system components,
123
process instruments, and appurtenances through which water flows
124
or comes into contact with chemical applicators, valves, pumps,
125
condensers, heat exchangers, and other related components.
126
(8) "Corrective action" means disinfection, cleaning,
127
flushing, and other activities to remedy biofilm growth,
128
Legionella proliferation, or other system mechanical problems
129
identified through monitoring, inspections, or other means, as
130
determined by the department.
131
(9) "Cycles of concentration" means the ratio of make-up
132
water volume to blowdown water volume which may be approximated
133
from the ratio of the conductivity of the blowdown water to the
134
conductivity of the make-up water.
135
(10) "Department" means the Department of Health.
136
(11) "Dip slide" means a method to test for microorganisms
137
which consists of a sterile culture medium affixed to a sterile
138
slide that is dipped directly into the sampled liquid.
139
(12) "Disinfection" means the use of one or more biocides
140
at a defined concentration, under specified conditions, for an
141
established period of time to kill or inactivate pathogenic
142
microorganisms. The term does not include the cleaning of a
143
cooling tower through the application of detergents, penetrants,
144
brushes or other tools, highly pressurized water, or any other
145
method that does not involve the use of a pesticide or economic
146
poison, as defined in s. 482.021(23); the use of a pesticide, as
147
defined in s. 487.021(49); or the use of a restricted-use
148
pesticide, as defined in s. 487.021(58).
149
(13) "Domestic water holding tank" means a fixed,
150
enclosed, above-ground or below-ground vessel that is designed,
151
constructed, and installed to store potable water intended for
152
human consumption, household use, or sanitary purposes within a
153
residential or mixed-use building.
154
(14) "Drift eliminator" means a system of baffles that
155
causes separation of entrained water designed to remove aerosols
156
from cooling tower exhaust.
157
(15) "Heterotrophic plate count" means a measure of the
158
concentration of microorganisms that require an external source
159
of organic carbon for growth, including bacteria, yeasts, and
160
mold, in water samples.
161
(16) "Legionella" means the genus of bacteria that is
162
ubiquitous in aqueous environments, including the recirculated
163
water of cooling tower water systems that are not properly or
164
regularly maintained.
165
(17) "Legionella culture sampling and analysis" means the
166
collection of a water sample for the measurement of the live
167
culture of Legionella involving the use of specialized media and
168
laboratory methods for growth to determine the species and
169
serogroup.
170
(18) "Maintenance program and plan" means a written
171
document, developed by a qualified person, which specifies
172
required monitoring, cleaning, disinfection, and other practices
173
for the prevention and control of Legionella growth in a cooling
174
tower water system, and is in accordance with sections 5, 6, and
175
7.2 of ANSI/ASHRAE Standard 188-2018, Legionellosis: Risk
176
Management for Building Water Systems and the manufacturer's
177
instructions.
178
(19) "Owner" means all of the following:
179
(a) A person, agent, firm, partnership, corporation, or
180
other legal entity that has a legal or equitable interest in, or
181
control of, a cooling tower or the premises of the cooling
182
tower.
183
(b) The legal owner of the building.
184
(c) A tenant, if the tenant:
185
1. Owns a cooling tower that services the tenant's leased
186
premises; or
187
2. Does not own the cooling tower but has a lease or
188
contractual arrangement to maintain the cooling tower.
189
(20) "Qualified person" means a professional engineer
190
licensed and registered in this state; a Class E water treatment
191
operator licensed and registered in this state; a certified
192
industrial hygienist; a certified water technologist; a
193
professional with training and experience in developing
194
management plans and performing inspections in accordance with
195
industry protocols, including, but not limited to, NSF Protocol
196
453-2017: Cooling Towers – Treatment, Operation, and Maintenance
197
to Prevent Legionellosis; or an environmental consultant who has
198
at least 2 years of operational experience in water management
199
planning and operation.
200
(21) "Supplemental disinfection system" means a
201
permanently installed treatment system designed to provide
202
additional microbial protection for potable water supplied to a
203
residence or residential facility. The system:
204
(a) May include chlorine, chlorine dioxide, or
205
monochloramine for chlorination or chloramine injection systems
206
and disinfection processes approved by the Department of
207
Environmental Protection for potable water use.
208
(b) Must be constructed of materials certified for contact
209
with drinking water and designed to operate within the
210
manufacturer's specified flow, pressure, and water quality
211
parameters.
212
(c) Must be installed in accordance with applicable
213
plumbing, electrical, and public health codes.
214
(d) Must incorporate appropriate monitoring; control; and
215
safety features, including alarms; dosage controls; fail-safe
216
shutdown mechanisms; and provisions to prevent contamination or
217
backflow into the potable water supply.
218
Section 4. Section 386.303, Florida Statutes, is created
219
to read:
220
386.303 Registration; reporting; recordkeeping.—
221
(1) REGISTRATION.—Before initial operation, and upon any
222
change in ownership, the owner of a cooling tower water system,
223
domestic water holding tank, or supplemental disinfection system
224
shall register each of his or her cooling tower water systems,
225
domestic water holding tanks, or supplemental disinfection
226
systems with the department using a statewide electronic system
227
designated by the department. The registration system must
228
require, at a minimum, all of the following information:
229
(a) The street address of the building at which the
230
cooling tower is located.
231
(b) The name, address, telephone number, and e-mail
232
address of each cooling tower owner.
233
(c) The total number of cooling towers, domestic water
234
holding tanks, or supplemental disinfection systems.
235
(d) The name of the manufacturer of the system.
236
(e) The model number of the system.
237
(f) The specific unit serial number of the system, if
238
available.
239
(g) The cooling capacity of the cooling tower in tons, the
240
volume of the domestic water holding tank in gallons, and the
241
total gallons treated yearly for the supplemental disinfection
242
system.
243
(h) The volume of the cooling tower water system,
244
inclusive of any piping, basin, or sump.
245
(i) The intended use of the cooling tower.
246
(j) Whether systematic disinfection in accordance with s.
247
386.307 is maintained manually, through timed injection, or
248
through continuous delivery.
249
(k) Whether maintenance is performed by an employee, a
250
contractor, or another party.
251
(l) The year the cooling tower was placed into service.
252
(2) REPORTING.—
253
(a) Beginning July 1, 2027, a cooling tower, domestic
254
water holding tank, or supplemental disinfection system owner
255
shall report through the statewide electronic system all of the
256
following information to the department at least every 90 days
257
while the cooling tower, domestic water holding tank, or
258
supplemental disinfection system is in use:
259
1. The date of the last bacteriological culture sample
260
collection, the results of the analysis, and the designated due
261
date of any remedial action that is required pursuant to s.
262
386.304(2)(a).
263
2. The date of the last Legionella culture sample
264
collection, the results of the sample analysis, and the date
265
that any remedial action was taken as required by s.
266
386.304(2)(b)-(e).
267
3. The date of the last compliance inspection performed
268
pursuant to s. 386.308 and the resulting standardized inspection
269
report.
270
4. The date of the lowest daily cycles of concentration
271
recorded, and the target number of cycles.
272
5. The average daily make-up water volume and blowdown
273
water volume.
274
6. The percentage of make-up water that is delivered to
275
the cooling tower versus the blowdown water volume.
276
7. The date of most recent certification pursuant to s.
277
386.308.
278
8. The date of removal or permanent discontinuation of use
279
of the cooling tower, if applicable.
280
9. Any other information deemed necessary by the
281
department.
282
(b) If a landlord and a tenant are considered to be owners
283
of a cooling tower, as defined in s. 386.302, only one of the
284
parties is required to register the cooling tower. However, both
285
parties are responsible for ensuring that registration and
286
reporting are completed as required by this part.
287
(3) STATEWIDE SYSTEM.—
288
(a) The department shall make the data in the statewide
289
electronic system:
290
1. Publicly available, as appropriate.
291
2. Fully accessible to and searchable by county health
292
departments.
293
(b) This part does not prohibit a county health department
294
or the Department of Agriculture and Consumer Services from
295
requiring registration with and reporting to a county system or
296
collecting fees associated with the administration of such a
297
system.
298
(c) The department shall provide owners with a mobile data
299
collection platform that is compatible with Android and Apple
300
devices and that electronically collects, and allows owners to
301
electronically submit, the information required by this part.
302
(4) RECORDKEEPING.—A cooling tower owner shall:
303
(a) Maintain for at least 3 years all of the following
304
records:
305
1. Required sampling and analyses.
306
2. Disinfection schedules and applications.
307
3. Inspection findings, deficiencies, and corrective
308
actions.
309
4. Required certifications.
310
(b) Maintain on the premises of the cooling tower a copy
311
of the current maintenance program and plan required by this
312
part.
313
(c) Make the records and plan required under this
314
subsection immediately available to the department or county
315
health department upon request.
316
Section 5. Section 386.304, Florida Statutes, is created
317
to read:
318
386.304 Maintenance program and plan.—
319
(1) The owner of a cooling tower shall:
320
(a) By September 1, 2027, develop or update a maintenance
321
program and plan for each existing cooling tower which must be
322
consistent with section 7.2 of ANSI/ASHRAE Standard 188-2018,
323
Legionellosis: Risk Management for Building Water Systems.
324
(b) After September 1, 2027, maintain such a maintenance
325
program and plan for each newly installed cooling tower.
326
(2) The maintenance program and plan must include all of
327
the following elements:
328
(a) A schedule for routine bacteriological culture
329
sampling and analysis to assess microbiological activity. The
330
sampling and analysis must be conducted at intervals of not more
331
than 28 days while the cooling tower is in use and must require
332
additional bacteriological culture sampling and analysis, as
333
needed, to validate process adjustments.
334
(b) A schedule for routine Legionella culture sampling and
335
analysis within 14 days after startup and, thereafter, while the
336
cooling tower is in use, at monthly intervals. Cooling towers in
337
use year-round must conduct sampling and analysis at intervals
338
of not more than 30 days and within 2 weeks after startup
339
following maintenance.
340
(c) A procedure for achieving water efficiency by
341
maintaining a minimum of three cycles of concentration using
342
automatic conductivity control or for estimating the percentage
343
of water savings through the installation of water meters on
344
make-up and blowdown lines.
345
(d) A requirement that, in addition to development of the
346
routine Legionella culture sampling and analysis schedule
347
required by paragraph (b), immediate Legionella culture sampling
348
and analysis be conducted in the event of any of the following:
349
1. A mechanical breakdown of the cooling tower water
350
system for more than 72 hours.
351
2. A power failure affecting the cooling tower system for
352
more than 72 hours.
353
3. A loss of biocide treatment of the cooling tower system
354
for more than 72 hours.
355
4. Failure of conductivity control or any other control
356
methods for more than 72 hours.
357
5. A determination by the department or a county health
358
department that one or more cases of legionellosis are or may be
359
associated with the cooling tower, based on epidemiologic data
360
or laboratory testing.
361
6. Any other conditions specified by the department or a
362
county health department.
363
(e) A requirement that an owner take immediate and
364
appropriate action, including remedial action, in response to a
365
bacteriological or Legionella culture analysis. For
366
bacteriological analysis results, the response must include, but
367
need not be limited to, taking action as required by s.
368
386.305(2). For Legionella culture analysis results, the
369
response must include, but need not be limited to, taking action
370
as required by s. 386.305(3) and contacting the county health
371
department as required by s. 386.306.
372
(f) A requirement that any Legionella culture analyses be
373
performed pursuant to s. 386.305(1).
374
(g) A shutdown and disinfection plan for removing or
375
permanently discontinuing use of a cooling tower.
376
(h) Requirements for treatment and manual or automated
377
flushing of any piping, basin, sump, or wetted surface during
378
idle conditions.
379
Section 6. Section 386.305, Florida Statutes, is created to read:
381
386.305 Culture analyses.—
382
(1) LABORATORY REQUIREMENTS.—A culture analysis must be
383
performed by an environmental laboratory certified pursuant to
384
s. 403.0625 which is approved to perform such an analysis.
385
(2) INTERPRETATION OF BACTERIOLOGICAL ANALYSIS RESULTS
386
FROM COOLING TOWERS.—
387
(a) Level 1.—Samples with a culture result that is less
388
than 10,000 colony-forming units per milliliter (CFU/mL). The
389
cooling tower owner shall maintain the treatment program and
390
bacteriological monitoring in accordance with the cooling
391
tower's maintenance program and plan.
392
(b) Level 2.—Samples with a culture result that is greater
393
than or equal to 10,000 CFU/mL but less than 100,000 CFU/mL. The
394
cooling tower owner shall do all of the following until the
395
water sample culture results meet the Level 1 criteria:
396
1. Review the treatment program.
397
2. Initiate immediate disinfection by increasing biocide
398
concentration or using a different biocide within 24 hours after
399
receiving the analysis results.
400
3. Retest the water within 3 to 7 days after receiving the
401
analysis results.
402
(c) Level 3.—Samples with a culture result that is greater
403
than or equal to 100,000 CFU/mL but less than 1,000,000 CFU/mL.
404
The cooling tower owner shall do all of the following until the
405
water sample culture results meet the Level 1 criteria:
406
1. Review the treatment program and provide notification
407
as required by s. 386.306.
408
2. Increase biocides within 24 hours after receiving the
409
analysis results.
410
3. Perform a visual inspection to evaluate the need to
411
perform cleaning and additional disinfection.
412
4. Retest the water within 3 to 7 days after receiving the
413
analysis results.
414
(d) Level 4.—Samples with a culture result that is greater
415
than or equal to 1,000,000 CFU/mL. The cooling tower owner shall
416
do all of the following until the water sample culture results
417
meet the Level 1 criteria:
418
1. Review the treatment program and provide notification
419
as required by s. 386.306.
420
2. Increase biocides within 2 hours after receiving the
421
analysis results.
422
3. Within 48 hours after receiving the analysis results,
423
perform remediation of the tower by hyper halogenating,
424
cleaning, and flushing the tower.
425
4. Retest the water within 3 to 7 days after receiving the
426
analysis results.
427
(3) INTERPRETATION OF LEGIONELLA CULTURE RESULTS FROM
428
COOLING TOWERS.—
429
(a) Level 1.—Legionella culture sample results of less
430
than 20 CFU/mL. The cooling tower owner shall maintain the
431
treatment program and monitoring in accordance with the
432
maintenance program and plan for the cooling tower.
433
(b) Level 2.—Legionella culture sample results of more
434
than or equal to 20 CFU/mL but less than 1,000 CFU/mL. The
435
cooling tower owner shall do all of the following until the
436
water sample culture results meet the Level 1 criteria:
437
1. Review the treatment program.
438
2. Perform immediate online disinfection.
439
3. Retest the water within 3 to 7 days after receiving the
440
analysis results.
441
a. If the retest indicates a presence of Legionella of
442
more than or equal to 20 CFU/mL but less than 100 CFU/mL, the
443
cooling tower owner must repeat the online disinfection.
444
b. If the subsequent retest indicates a presence of
445
Legionella of more than or equal to 100 CFU/mL but less than
446
1,000 CFU/mL, the cooling tower owner must further investigate
447
the water treatment program and immediately perform online
448
disinfection.
449
(c) Level 3.—Legionella culture sample results of more
450
than or equal to 1,000 CFU/mL. The cooling tower owner shall do
451
all of the following until the water sample culture results meet
452
the Level 1 criteria:
453
1. Review the treatment program.
454
2. Provide notification as required by s. 386.306.
455
3. Institute immediate system decontamination.
456
4. Retest the water within 3 to 7 days after receiving the
457
analysis results.
458
a. If the retest indicates a presence of Legionella of
459
more than or equal to 20 CFU/mL but less than 1,000 CFU/mL, the
460
cooling tower owner must take the actions required under
461
paragraph (b).
462
b. If the subsequent retest indicates a presence of
463
Legionella of more than or equal to 1,000 CFU/mL, the owner must
464
perform system decontamination. Section 7. Section 386.306, Florida Statutes, is created
466
to read:
467
386.306 Notification.—A cooling tower owner shall:
468
(1) Notify the county health department within 24 hours
469
after receiving a Legionella water sample culture result that
470
exceeds 1,000 colony-forming units per milliliter. The county
471
health department shall notify the department within 24 hours
472
after receiving such a report.
473
(2) Notify the public of such test results in a manner
474
determined by the county health department or, at the discretion
475
of the department, by the department.
476
Section 8. Section 386.307, Florida Statutes, is created
477
to read:
478
386.307 Cooling tower standards.—
479
(1) DISINFECTION.—
480
(a) A person who disinfects a cooling tower must be a
481
commercial applicator or a certified applicator as defined in s.
482
487.021 who is licensed to apply biocide in a cooling tower and
483
who is certified in accordance with the requirements of the
484
Florida Pesticide Law, or be an apprentice who is under the
485
direct supervision of a licensed applicator, as defined in s.
486
487.021.
487
(b) The cooling tower owner shall maintain the name and
488
certification number of the applicator who disinfects the
489
cooling tower under paragraph (a) or the business name and
490
number of the company providing onsite disinfection.
491
(c) Only biocide products registered by the Department of
492
Environmental Protection for use in cooling towers or pesticidal
493
devices produced in an establishment registered by the
494
Environmental Protection Agency may be used to disinfect a
495
cooling tower.
496
(2) EFFICIENCY.—
497
(a) Each cooling tower owner shall install make-up and
498
blowdown meters on each of his, her, or its cooling towers to
499
monitor the total volume of water used by the cooling tower and
500
shall ensure that the cooling tower has an automatic
501
conductivity controller, a high-efficiency drift eliminator, and
502
an overflow alarm to prevent overflow of the sump in case of
503
make-up water valve failure. The overflow alarm must provide an
504
alert through an energy management control system to the cooling
505
tower operators in the event of an overflow of the sump.
506
(b) All cooling towers must achieve at least eight cycles
507
of concentration using automatic conductivity control.
508
(c) The efficiency of the cooling tower water system must
509
be measured by the percentage of water that is delivered to the
510
cooling tower versus the blowdown water volume.
511
(d) If the local water utility supplies water to the
512
property, water meters must meet the requirements of the
513
utility.
514
Section 9. Section 386.308, Florida Statutes, is created to read:
516
386.308 Compliance inspection and certification.—
517
(1) COMPLIANCE INSPECTION.—
518
(a) Each cooling tower owner shall ensure that each of
519
his, her, or its cooling towers is inspected before initial
520
startup and at intervals of not more than every 90 days while in
521
use.
522
(b) A compliance inspection must be performed by a
523
qualified person who is unaffiliated with the water treatment
524
company; a professional engineer licensed in this state; an
525
industrial hygienist; a water technologist; or an environmental
526
consultant, any of whom must have training and experience in
527
performing inspections in accordance with current standard
528
industry protocols, including, but not limited to, ANSI/ASHRAE
529
Standard 188-2018, Legionellosis: Risk Management for Building
530
Water Systems.
531
(c) Each compliance inspection must include an evaluation,
532
on a standardized inspection form created by the department, of
533
all of the following:
534
1. The cooling tower and associated equipment for the
535
presence of organic material, biofilm, algae, debris, and other
536
visible contaminants.
537
2. The general condition of the cooling tower basin,
538
remote sump, packing material, and drift eliminators.
539
3. The water make-up connections and control, including
540
backflow protection or air gaps, as needed.
541
4. Whether the conductivity control and the make-up and
542
blowdown meters are functioning properly.
543
5. Whether the water treatment equipment, including, but
544
not limited to, pumps, timers, valves, and strain gauges, are
545
functioning properly.
546
(d) Information collected during compliance inspections
547
must be collected and entered into the department's mobile data
548
collection platform, must include the standardized inspection
549
form, and must be submitted to the registration portal by a
550
qualified person as specified in paragraph (b).
551
(e) The person performing the inspection shall report any
552
deficiencies found to the owner so that corrective action may be
553
taken and document all completed corrective actions using the
554
department's mobile data collection platform.
555
(2) CERTIFICATION.—By November 1, 2026, and by each
556
November 1 thereafter, a cooling tower owner shall obtain an
557
annual certification from a qualified person which certifies
558
that a maintenance program and plan is in place for the cooling
559
tower and that all actions required under that plan and this
560
part have been taken, including, but not limited to, all of the
561
following:
562
(a) All required bacteriological culture sampling and
563
analyses.
564
(b) All Legionella culture sampling and analyses,
565
including any immediate Legionella culture sampling and analyses
566
performed pursuant to s. 386.304(2)(d) and (e).
567
(c) Any disinfection performed pursuant to the standards
568
specified in s. 386.307(1).
569
(d) All compliance inspections performed pursuant to
570
subsection (1).
571
(3) REPORTING.—All inspection findings, deficiencies,
572
corrective actions, and certifications must be reported to the
573
department and maintained by the owner as required by s.
574
386.303.
575
Section 10. Section 386.309, Florida Statutes, is created
576
to read:
577
386.309 Enforcement.—
578
(1) The department or a county health department may
579
require an owner to conduct Legionella culture sampling and
580
analysis following a determination, based on epidemiologic data
581
or laboratory testing, that one or more cases of legionellosis
582
are or may be associated with a cooling tower.
583
(2) An officer, employee, or agent of the department or
584
the county health department may enter onto any property to
585
inspect a cooling tower for compliance with this part and may
586
take water samples as part of such inspections. Such inspections
587
must be conducted as provided in s. 487.071.
588
(3) If an owner fails to register a cooling tower, develop
589
and maintain a maintenance program and plan for a cooling tower,
590
obtain certification for a cooling tower, disinfect a cooling
591
tower, perform or obtain required culture sampling and analysis,
592
or conduct inspections of a cooling tower as required in this
593
part, the department or the county health department may
594
determine that such failure constitutes a nuisance pursuant to
595
this chapter.
596
(4) An owner who violates this part is subject to civil
597
and criminal penalties as provided in s. 386.051. Each day that
598
an owner remains in violation of this part constitutes a
599
separate offense.
600
(5) The State Surgeon General shall submit a report to the
601
President of the Senate and the Speaker of the House of
602
Representatives by each January 1 which includes all of the
603
following information:
604
(a) For the prior year:
605
1. The number of new cooling tower registrations issued
606
and the number of notifications of discontinued use of a cooling
607
tower received by the department pursuant to s. 386.303 as of
608
November 1.
609
2. The number of annual certifications that a cooling
610
tower was inspected, tested, cleaned, and disinfected received
611
by the department pursuant to s. 386.308 as of November 1.
612
3. The number of reports of tests for the presence of
613
Legionella which reported levels above 1,000 CFU/mL received by
614
the department.
615
4. The number of inspections of cooling towers conducted
616
by the department, or a county health department on behalf of
617
the department, along with the number and types of any
618
violations cited during such inspections.
619
5. The number of cleanings, disinfections, or other
620
actions performed by or on behalf of the department.
621
6. The number of persons diagnosed with legionellosis in
622
this state to the extent known or reasonably discoverable by the
623
department.
624
(b) Recommendations as to whether department rules should
625
be amended to include requirements for any of the building water
626
systems described in ANSI/ASHRAE Standard 188-2018,
627
Legionellosis: Risk Management for Building Water Systems.
628
(c) Information regarding the implementation of any such
629
requirements, their effectiveness in preventing outbreaks of
630
legionellosis, and recommendations for improvements or
631
modifications to department rules to further the control of
632
Legionella.
633
Section 11. Section 386.3101, Florida Statutes, is created
634
to read:
635
386.3101 Waivers.—The department may issue a written
636
general or specific waiver with respect to this part if the
637
department determines that such waiver will not present a danger
638
to public health. The department may revoke the waiver upon a
639
determination that the waiver may present a danger to public
640
health.
641
Section 12. Until December 31, 2027, an owner may submit a
642
written application to a county health department for a variance
643
from any requirement of this part for additional time to come
644
into compliance with this act. A variance may not exceed 90
645
days. The application must include an explanation as to why the
646
variance will not present a danger to public health. With the
647
approval of the Department of Health, the county health
648
department may approve such application for a variance in
649
writing, subject to any conditions that the department or county
650
health department may deem appropriate to protect public health.
651
The department or the county health department may revoke a
652
variance upon a determination that the variance may present a
653
danger to public health.
654
Section 13. This act shall take effect July 1, 2026.